  1 new product news solid-state timers h3dk din track-mounted, 22.5-mm-width standard timer series ? a wide ac/dc power supply range (24 to 240 vac/dc).* 1 ? all sub-series include models with 12-vdc power supply.* 1 ? g-type models (h3dk-g) now include model with 240 to 440- vac power supply. ?ul* 2 , csa* 3 , and ccc certification and en 61812-1 compliance. ce marking. ? emc (en 61812-1) compliance for application in heavy industri- al, residential, commercial, or light industrial environments. ? finger-safe terminal block and captive screws according to en 50274. *1. except for the h3dk-h. *2. except for the h3dk-ge. *3. scheduled to obtain certification in april 2012. lr model number structure the entire h3dk series model number legend (not all models that can be represented with the model number legend can necessarily be produced.) h3dk series h3dk-m/-s m u lti-range, m u lti-mode timers eight-mode timer h3dk-m1/m2 operating modes a: o n delay b: flicker off start b2: flicker o n start c: signal o n /off delay d: signal off delay e: interval g: signal o n /off delay j: one-shot o u tp u t fo u r-mode timer h3dk-s1/s2 operating modes a: o n delay b2: flicker o n start e: interval j: one-shot o u tp u t h3dk-f t w in timers h3dk-h po w er off-delay timers h3dk-g star-delta timers operating modes po w er off-delay timer operating modes star-delta timer operating modes flicker-off start/ flicker-o n start page 2 page 11 page 15 page 21 1234 h3dk- @@@@ 1. type 2. control output * m- and s-type models only. 3. supply voltage *1 h-type models only. *2 g-type models only. 4. time ranges (h-type models only) symbol meaning m eight-mode timer s four-mode timer f twin timer g star-delta timer h power off-delay timer symbol meaning 1 spdt 2dpdt symbol meaning blank 24 to 240 vac/dc a12 vdc b 24 to 48 vac/dc c *1 100 to 120 vac d *1 200 to 240 vac e *1 240 to 440 vac *2 symbol meaning s 0.1 to 1.2 s or 1 to 12 s l 1 to 12 s or 10 to 120 s
2 new product news multi-range, multi-mode timer h3dk-m/h3dk-s  multiple time ranges and operating modes let you cover a wide range of applications.  the time-limit dpdt output contac ts can be change d to time-limit spdt and instantaneous spdt outp ut contacts using a switch.  sequence checks are easily perfor med by setting an instanta- neous output to 0.  start signal control for the h3dk-m. lr ordering information list of models accessories (order separately) model structure supply voltage control output eight-mode timer four-mode timer 24 to 240 vac/dc contact output, dpdt (time-limit dpdt, or time-limit spdt + instantaneous spdt) changed using a switch. model h3dk-m2 h3dk-s2 contact output, spdt (time-limit spdt) model h3dk-m1 h3dk-s1 12 vdc contact output, dpdt (time-limit dpdt, or time-limit spdt + instantaneous spdt) changed using a switch. model h3dk-m2a h3dk-s2a contact output, spdt (time-limit spdt) model h3dk-m1a h3dk-s1a item specification model mounting track 50 cm (l) x 7.3 mm (t) pfp-50n 1 m (l) x 7.3 mm (t) pfp-100n 1 m (l) x 16 mm (t) pfp-100n2 end plate --- pfp-m spacer --- pfp-s model operating modes terminal block input type output type mounting method safety standards accessories h3dk-m2 a: on delay b: flicker off start b2: flicker on start c: signal on/off delay d: signal off delay e: interval g: signal on/off delay j: one-shot output 9 terminals voltage input relay, dpdt din track mounting curus (ul 508 csa c22.2 no. 14) en 61812-1 iec 60664-1 4 kv/2 en 50274 user label h3dk-m1 relay, spdt h3dk-s2 a: on delay b2: flicker on start e: interval j: one-shot output --- relay, dpdt h3dk-s1 6 terminals relay, spdt
h3dk-m/h3dk-s 3 specifications time ranges ratings time range setting 0.1 s 1 s 10 s 1 min 10 min 1 h 10 h 100 h set time range 0.1 to 1.2 s 1 to 12 s 10 to 120 s 1 to 12 min 10 to 120 min 1 to 12 h 10 to 120 h 100 to 1,200 h scale numbers 12 power supply voltage *1 ? 24 to 240 vac/dc, 50/60 hz *2  12 vdc *2 allowable voltage fluctuation range  24 to 240 vac/dc: 85% to 110% of rated voltage  12 vdc: 90% to 110% of rated voltage power reset minimum power-off time: 0.1 s reset voltage 10% of rated voltage voltage input  24 to 240 vac/dc high level: 20.4 to 264 vac/dc, low level: 0 to 2.4 vac/dc  12 vdc high level: 10.8 to 13.2 vdc, low level: 0 to 1.2 vdc *3 power con- sumption h3dk-m2/-s2 at 240 vac: 6.6 va max. *4 h3dk-m1/-s1 at 240 vac: 4.5 va max. *4 h3dk-m2a/-s2a at 12 vdc: 0.9 w max. h3dk-m1a/-s1a at 12 vdc: 0.6 w max. control output contact output, 5 a at 250 vac with resistive load (cos = 1), 5 a at 30 vdc with resistive load *4, *5 ambient operating temperature ?20 to 55 c (with no icing) storage temperature ?40 to 70 c (with no icing) ambient operating humidity 25% to 85% *1. when using a 24-vdc power supply voltage, there will be an inrush current of approximately 0.25 a. allow fo r this inrush current when turning on and off the power supply to the timer with device with a solid- state output, such as a sensor. *2. dc ripple: 20% max. *3. the power consumption is for mode a after the time r times out. for the h3dk-m @ , the maximum power consumption is given, including the current consumed by the input circuit. *4. refer to dc power consumptions (reference infor - mation) on page 27 for dc power consumptions. *5. the control output ratings are for one h3dk operating alone. if you operate two or more timers side by side, refer to installation pitch and output switching capac - ity (reference values) on the next page. *6. 125 vdc: 0.15 a max. with resistive load, 125 vdc: 0.1 a with l/r of 7 ms. minimum load: 10 ma at 5 vdc (p level, reference value)
h3dk-m/h3dk-s 4 characteristics i/o * if the inst/time switch on the front of the timer is set to inst on the h3dk-m2/-s2, relay r2 will operate as instantaneous contacts and will turn on/off in synchronization with the power supply. item model h3dk-m1/-m2 h3dk-s1/-s2 input start functions to start timing. there is no start input. output control output the output is turned on/off according to the operating mode when the value that is set on the dial is reached. * installation pitch and output switching capacity (reference val- ues) the relation between the installation pitch and the load current is shown in the follow- ing graph. (except for the h3dk-ge) if timer is used under load conditions that exceed the specified values, the tempera- ture inside the timer will increase, reducing the life expectancy of internal parts. 0 1 2 3 4 5 6 80 70 60 50 40 30 20 10 d = 5 mm d=0 a d = 10 mm d = 50 mm ambient temperature (c) maximum ambient operating temperature in specifications load current (a) din track timer installation pitch: d tested timer: h3dk-m/-s applied voltage: 240 vac installation pitch: 0, 5, 10, and 50 mm test timer 1 test timer 2 test timer 3 te s t timer 4 te s t timer 5 testing method * with the h3dk-m @ , if the voltage exceeds 26.4 vac/dc in mode c, d, or g, the off trigger signal char- acteristics are as follows: accuracy of operating time: 1% 50 ms max. setting error: 10% max. minimum input signal width: 100 ms applicable standards accuracy of operating time 1% of fs max. ( 1% 10 ms max. at 1.2-s range)* setting error 10% of fs 0.05 s max.* minimum input signal width 50 ms* (start input) influence of voltage 0.5% of fs max. ( 0.5% 10 ms max. at 1.2-s range) influence of tempera- ture 2% of fs max. ( 2% 10 ms max. at 1.2-s range) insulation resistance 100 m ? min. at 500 vdc dielectric strength between current-carrying metal parts and exposed non-current-carrying metal parts: 2,000 vac 50/60 hz for 1 min. between control output terminals and operating circuit: 2,000 vac 50/60 hz for 1 min. between contacts not located next to each other: 1,000 vac 50/60 hz for 1min. impulse withstand volt- age 24 to 240 vac/vdc: 3 kv between power terminals, 4.5 kv between current- carrying metal parts and exposed non-current-carrying metal parts 12 vdc: 1 kv between power terminals, 1.5 kv between current-carrying metal parts and exposed non-current-carrying metal parts noise immunity square-wave noise generated by noise simulator (pulse width: 100 ns/1 s, 1-ns rise): 1.5 kv static immunity malfunction: 4 kv, destruction: 8 kv vibration resistance destruction 0.75-mm single amplitude at 10 to 55 hz for 2 h each in 3 directions malfunction 0.5-mm single amplitude at 10 to 55 hz for 10 min each in 3 directions shock re- sistance destruction 1,000 m/s 2 3 times each in 6 directions malfunction 100 m/s 2 3 times each in 6 directions life ex- pectancy mechanical 10 million operations min. (under no load at 1,800 operations/h) electrical 100,000 operations min. (5 a at 250 vac, resistive load at 360 operations/h) degree of protection ip30 (terminal block: ip20) weight approx. 120 g safety standards curus: ul 508/csa c22.2 no. 14 en 50274: finger protection, back-of-hand proof en 61812-1: pollution degree 2, overvoltage category iii ccc: pollution degree 2, overvoltage category ii, section db14048.5-2008 part 5-1 lr: test specification no. 1-2002 category env 1.2 emc (emi) en61812-1 radiated emissions: en 55011 class b emission ac mains: en 55011 class b harmonic current: en 61000-3-2 voltage fluctuations and flicker: en61000-3-3 (ems) en61812-1 esd immunity: en 61000-4-2: 6 kv contact discharge, 8 kv air discharge radiated radio-frequency electromagnetic field immunity (am radio waves): en 61000-4-3: 10 v/m (80 mhz to 1 ghz) burst immunity: en 61000-4-4: 2 kv power line, 1 kv i/o signal line surge immunity: en 61000-4-5: 2 kv common mode, 1 kv differential mode + 100 ms ? 50 ms
h3dk-m/h3dk-s 5 connections block diagrams h3dk-m1/-m2 h3dk-s1/-s2 output circuit ram rom indicator circuit input circuit power supply circuit ac (dc) input start input power indicator output indicator time setting detection circuit time specification switches operating mode switch one-chip microcomputer clock output circuit indicator circuit power supply circuit ac (dc) input power indicator output indicator time setting detection circuit time specification switches operating mode switch ram rom one-chip microcomputer clock
h3dk-m/h3dk-s 6 terminal arrangement input connections the start input of the h3dk-m1/-m2 is a voltage input. a1 15 b1 a2 18 16 a1 15 25/21 b1 26/22 28/24 a2 18 16 a1 15 25/21 26/22 28/24 a2 18 16 a1 15 a2 18 16 15 r1 1618 15 r1 1618 25/21 r2 * 26/22 28/24 15 r1 1618 15 r1 1618 25/21 r2 * 26/22 28/24 h3dk-m1 h3dk-m2 h3dk-s1 h3dk-s2 start see note 3. (din notation) (din notation) (din notation) (din notation) start see note 3. see note 3. see note 3. a2 a1 15 1816 b1 a2 a1 15 1816 b1 (21) 25 28 (24) 26 (22) a2 a1 15 1816 a2 a1 15 1816 (21) 25 28 (24) 26 (22) note 1: the time-limit contact symbol for previous models of timers was . the time-limit contact symbol for the h3dk is . a different symbol is used because the h3dk supports multiple operating modes. note 2: *the relay r2 can be set to either instantaneous or time-limit contacts using the switch on the front of the timer. note 3: the power supply terminals do not have polarity. sensor timer a1 (+) a2 (?) b1 start 24 vdc 24 vdc (sensor power supply) (+) (?) sensor timer a1 ( ?) a2 (+) b1 start 24 vdc (?) (+) timer a1 a2 b1 start operates when pnp transistor turns on. operates when npn transistor turns on. operates when relay turns on. 24 vdc (sensor power supply) voltage input signal levels tran- sistor input 1. transistor on  residual voltage: 1 v max. voltage between terminals b1 and a2 must be equal to or higher than the rated high level voltage (20.4 vdc min.). 2. transistor off  leakage current: 0.01 ma max. voltage between terminals b1 and a2 must be equal to or below the rated low level voltage (2.4 vdc min.). relay input use relays that can adequately switch 0.1 ma at the imposed voltage. when the relay is on or off, the voltage between terminals b1 and a2 must be within the following ranges:  24 to 240 vac/dc when relay is on: 20.4 to 264 vac/dc when relay is off: 0 to 2.4 v  12 vdc when relay is on: 10.8 to 13.2 v when relay is off: 0 to 1.2 v pnp transistor input npn transistor input relay input consider the minimum load of the relay. (see signal levels on the right.)
h3dk-m/h3dk-s 7 nomenclature *if the switch is left between settings, proper operation may not be possible. make sure that the switch is set properly. note: the default settings are for 0.1 s in mode a. terminal block (see notes 1 and 2.) bottom view front view time range switch operating mode switch output indicator (orange) (lit while timer gives output.) operation/power indicator (green) (lit while the power is on.) init/time switch for relay r2 (default setting is for time-limit output.)* main dial (for setting the time) user label attachment location note 1. use solid wire (2.5 mm 2 max.) or fer- rules with insulative sleeves to connect to the terminals. to maintain the withstand voltage after connecting the terminals, insert no more than 8 mm of exposed conductor into the terminal. recommended ferrules phoenix contact ai @@@ series ai-twin @@@ series note 2. screw tightening torque recommended torque: 0.49 nm maximum torque: 0.98 nm 8 mm max. 8 mm max. using solid wire (2.5 mm 2 max.) using ferrule with insulative sleeve h3dk-m2 h3dk-s2 user label attachment location main dial (for setting the time) front view time range switch output indicator (orange) (lit while timer gives output.) operation/power indicator (green) (lit while the power is on.) operating mode switch *if the switch is left between settings, proper operation may not be possible. make sure that the switch is set properly. note: the default settings are for 0.1 s in mode a. user label attachment location main dial (for setting the time) front view time range switch* output indicator (orange) (lit while timer gives output.) operation/power indicator (green) (lit while the power is on.) operating mode switch* *if the switch is left between settings, proper operation may not be possible. make sure that the switch is set properly. note: the default settings are for 0.1 s in mode a. h3dk-m1 h3dk-s1
h3dk-m/h3dk-s 8 dimensions (unit: mm) timers track mounting products (sold separately) refer to page 28 for details. operating procedures basic operation setting switches  each switch has a snap mechanism that secures the switch at given positions. set the switch to one of these positions. do not set it midway between two positions. malfunction could result from an improper setting. h3dk-m1 h3dk-s1 89.4 100 88.2 22.5 22.5 69.1 79 h3dk-m2 h3dk-s2 h3dk-m1 65.6 52 4 22.5 h3dk-s1 h3dk-m h3dk-s h3dk-m2 h3dk-s2 setting the operating mode the h3dk-m can be set to any of eight operating modes. the h3dk-s can be set to any of four operating modes. turn the operating mode switch with a flat- blade or phillips screwdriver. the h3dk- m can be set to any of eight modes; the h3dk-s, to any of four modes. switching relay r2 between instantaneous and time-limit contacts (h3dk-m2/-s2 only) the init/time switch can be used to switch relay r2 between instantaneous and time-limit operation. setting the time range the time range switch can be used to set the time range. turn the switch with a flat-blade or phillips screwdriver. setting the operating mode operating mode switch setting the init/time switch init/time switch setting the time range time range switch
h3dk-m/h3dk-s 9 timing charts  there is no start input with the h3dk-s. time r operation starts when the power is turned on.  there is no instantaneous output with the h3dk- @ 1. note 1.the reset time is 0.1 s min. make sure the signal input time is 0.05 s or longer. note 2.?t? is the set time. ?t ? a? is a time that is less that the set time. a: on delay b: flicker off start b2: flicker on start c: signal on/ off delay t t?a t power (a1 and a2) start (b1 and a1) time-limit contacts: nc 15 and 16 (25 and 26) time-limit contacts: no (output indicator) 15 and 18 (25 and 28) instantaneous contacts: nc (21 and 22) instantaneous contacts: no (21 and 24) power indicator power * start input output timing ** * for power on-delay operation, connect start input terminals b1 and a1. the timer starts operating as soon as the power turns on. ** the start input is ignored while the timer is in operation. basic operation tt ttt t?a t?a power (a1 and a2) start (b1 and a1) time-limit contacts: nc 15 and 16 (25 and 26) time-limit contacts: no (output indicator) 15 and 18 (25 and 28) instantaneous contacts: nc (21 and 22) instantaneous contacts: no (21 and 24) power indicator power * start input output timing ** * to start with the power supply, connect start input terminals b1 and a1. the timer starts operating as soon as the power turns on. ** the start input is ignored while the timer is in operation. timing timing timing basic operation tt ttt t?a t?a power (a1 and a2) start (b1 and a1) time-limit contacts: nc 15 and 16 (25 and 26) time-limit contacts: no (output indicator) 15 and 18 (25 and 28) instantaneous contacts: nc (21 and 22) instantaneous contacts: no (21 and 24) power indicator power * start input output timing ** * to start with the power supply, connect start input terminals b1 and a1. the timer starts operating as soon as the power turns on. ** the start input is ignored while the timer is in operation. timing timing timing basic operation tttt t?a t?a power (a1 and a2) start (b1 and a1) time-limit contacts: nc 15 and 16 (25 and 26) time-limit contacts: no (output indicator) 15 and 18 (25 and 28) instantaneous contacts: nc (21 and 22) instantaneous contacts: no (21 and 24) power indicator power * start input output timing * the start input is valid while the timer is in operation. timing timing timing basic operation
h3dk-m/h3dk-s 10 note 1.the reset time is 0.1 s min. make sure the signal input time is 0.05 s or longer. note 2.?t? is the set time. ?t ? a? is a time that is less that the set time. d: signal off delay e: interval g: signal on/ off delay j: one-shot output (on delay) tt t?a power (a1 and a2) start (b1 and a1) time-limit contacts: nc 15 and 16 (25 and 26) time-limit contacts: no (output indicator) 15 and 18 (25 and 28) instantaneous contacts: nc (21 and 22) instantaneous contacts: no (21 and 24) power indicator t?a t?a power * start input output * the start input is valid while the timer is in operation. timing basic operation tt t t?a power (a1 and a2) start (b1 and a1) time-limit contacts: nc 15 and 16 (25 and 26) time-limit contacts: no (output indicator) 15 and 18 (25 and 28) instantaneous contacts: nc (21 and 22) instantaneous contacts: no (21 and 24) power indicator t?a power * start input output timing ** * for power on-delay operation, connect start input terminals b1 and a1. the timer starts operating as soon as the power turns on. ** the start input is valid while the timer is in operation. basic operation tttt t?a power (a1 and a2) start (b1 and a1) time-limit contacts: nc 15 and 16 (25 and 26) time-limit contacts: no (output indicator) 15 and 18 (25 and 28) instantaneous contacts: nc (21 and 22) instantaneous contacts: no (21 and 24) power indicator t?a power start input output * * the start input is valid while the timer is in operation. timing timing timing timing basic operation tt t 1 s0.6 s (fixed) 1 s0.6 s (fixed) 1 s0.6 s (fixed) t?a power (a1 and a2) start (b1 and a1) time-limit contacts: nc 15 and 16 (25 and 26) time-limit contacts: no (output indicator) 15 and 18 (25 and 28) instantaneous contacts: nc (21 and 22) instantaneous contacts: no (21 and 24) power indicator t?a power * start input output timing ** * to start with the power supply, connect start input terminals b1 and a1. the timer starts operating as soon as the power turns on. ** the start input is valid while the timer is in operation. 1 s0.6 s (fixed) basic operation
11 new product news twin timer h3dk-f  switch between flicker-off or flicker-on start mode.  independent on time and off time settings.  eight time ranges from 0.1 s to 1,200 h. lr ordering information list of models accessories (order separately) model structure specifications time ranges ratings operating modes supply voltage control output h3dk-f flicker off start/flicker on start 24 to 240 vac/dc contact out- put: spdt model h3dk-f 12 vdc contact out- put: spdt model h3dk-fa item specification model mounting track 50 cm (l) x 7.3 mm (t) pfp-50n 1 m (l) x 7.3 mm (t) pfp-100n 1 m (l) x 16 mm (t) pfp-100n2 end plate --- pfp-m spacer --- pfp-s model operating modes terminal block output type mounting method safety standards accessories h3dk-f flicker off start/flicker on start 6 terminals relay, spdt din track mounting curus (ul508 csa c22.2 no. 14) en 61812-1 iec 60664-1 4 kv/2 en 50274 user label time range setting 0.1 s 1 s 10 s 1 min 10 min 1 h 10 h 100 h set time range 0.1 to 1.2 s 1 to 12 s 10 to 120 s 1 to 12 min 10 to 120 min 1 to 12 h 10 to 120 h 100 to 1,200 h scale numbers 12 power supply voltage *1  24 to 240 vac/dc, 50/60 hz *2  12 vdc *2 allowable voltage fluctuation range  24 to 240 vac/dc: 85% to 110% of rated voltage  12 vdc: 90% to 110% of rated voltage power reset minimum power-off time: 0.1 s reset voltage 10% of rated voltage power consumption h3dk-f at 240 vac: 4.5va max. *3 h3dk-fa at 12 vdc: 0.6 w max. control output contact output (spdt): 5 a at 250 vac with resistive load (cos = 1) 5 a at 24 vdc with resistive load *3, *4 ambient operating temperature ? 20 to 55 c (with no icing) storage temperature ? 40 to 70 c (with no icing) ambient operating humidity 25% to 85%
h3dk-f 12 *1. when using a 24-vdc power supply voltage, there will be an inrush current of approximately 0.25 a. allow for this inrush cur rent when turning on and off the power supply to the timer with device with a solid-state output, such as a sensor. *2. dc ripple: 20% max. *3. refer to dc power consumptions (reference information) on page 27 for dc power consumptions. *4. the control output ratings are for one h3dk operating alone. if you operate two or more timers side by side, refer to installation pitch and output switching capacity (reference values) on the next page. *5. 125 vdc: 0.15 a max. with resistive load, 125 vdc: 0.1 a with l/r of 7 ms. minimum load: 10 ma at 5 vdc (p level, reference value) characteristics installation pitch and output switching capacity (reference values) the relation between the installation pitch and the load current is shown in the follow- ing graph. (except for the h3dk-ge) if timer is used under load conditions that exceed the specified values, the tempera- ture inside the timer will increase, reduc- ing the life expectancy of internal parts. 0 1 2 3 4 5 6 80 70 60 50 40 30 20 10 d = 5 mm d = 0 mm d = 10 mm d = 50 mm ambient temperature (c) maximum ambient operating temperature in specifications load current (a) din track timer installation pitch: d tested timer: h3dk-f applied voltage: 240 vac installation pitch: 0, 5, 10, and 50 mm test timer 1 test timer 2 test timer 3 te s t timer 4 te s t timer 5 testing method applicable standards i/o accuracy of operating time 1% of fs max. ( 1% 10 ms max. at 1.2-s range) setting error 10% of fs 0.05 s max. influence of voltage 0.5% of fs max. ( 0.5% 10 ms max. at 1.2-s range) influence of tempera- ture 2% of fs max. ( 2% 10 ms max. at 1.2-s range) insulation resistance 100 m ? min. at 500 vdc dielectric strength between current-carrying metal parts and exposed non-current-carrying metal parts: 2,000 vac 50/60 hz for 1 min. between control output terminals and operating circuit: 2,000 vac 50/60 hz for 1 min. between contacts not located next to each other: 1,000 vac 50/60 hz for 1min. impulse withstand volt- age 24 to 240 vac/vdc: 3 kv between power terminals, 4.5 kv between current- carrying metal parts and exposed non-current-carrying metal parts 12 vdc: 1 kv between power terminals, 1.5 kv between current-carrying metal parts and exposed non-current-carrying metal parts noise immunity square-wave noise generated by noise simulator (pulse width: 100 ns/1 s, 1-ns rise): 1.5 kv static immunity malfunction: 4 kv, destruction: 8 kv vibration resistance destruction 0.75-mm single amplitude at 10 to 55 hz for 2 h each in 3 directions malfunction 0.5-mm single amplitude at 10 to 55 hz for 10 min each in 3 directions shock re- sistance destruction 1,000 m/s 2 3 times each in 6 directions malfunction 100 m/s 2 3 times each in 6 directions life ex- pectancy mechanical 10 million operations min. (under no load at 1,800 operations/h) electrical 100,000 operations min. (5 a at 250 vac, resistive load at 360 operations/h) degree of protection ip30 (terminal block: ip20) weight approx. 110 g safety standards curus: ul 508/csa c22.2 no. 14 en 50274: finger protection, back-of-hand proof en 61812-1: pollution degree 2, overvoltage category iii ccc: pollution degree 2, overvoltage category ii, section db14048.5-2008 part 5-1 lr: test specification no. 1-2002 category env 1.2 emc (emi) en61812-1 radiated emissions: en 55011 class b emission ac mains: en 55011 class b harmonic current: en 61000-3-2 voltage fluctuations and flicker: en61000-3-3 (ems) en61812-1 esd immunity: en 61000-4-2: 6 kv contact discharge, 8 kv air discharge radiated radio-frequency electromagnetic field immunity (am radio waves): en 61000-4-3: 10 v/m (80 mhz to 1 ghz) burst immunity: en 61000-4-4: 2 kv power line, 1 kv i/o signal line surge immunity: en 61000-4-5: 2 kv common mode, 1 kv differential mode input none output control output output is turned on/off according to the time set on the on time setting dial and off time setting dial.
h3dk-f 13 connections nomenclature block diagrams h3dk-f ac (dc) input on indicator off indicator one-chip microcomputer output circuit indicator circuit ram rom clock on/off start switch power supply circuit time specification switches on/off time setting detection circuit terminal arrangement h3dk-f note: the power supply terminals do not have po- larity. a1 15 a2 18 16 15 r1 1618 a2 a1 15 1816 (din notation) terminal block (see notes 1 and 2.) on time range switch bottom view front view on time setting dial (sets the on time.) off time setting dial (sets the off time.) on output indicator (orange) off output indicator (green) off time range switch on/off start switch (default setting is for an off start.) user label attachment location h3dk-f note 1. use solid wire (2.5 mm 2 max.) or fer- rules with insulative sleeves to connect to the terminals. to maintain the withstand voltage after connecting the terminals, insert no more than 8 mm of exposed conductor into the terminal. recommended ferrules phoenix contact ai @@@ series ai-twin @@@ series note 2. screw tightening torque recommended torque: 0.49 nm maximum torque: 0.98 nm 8 mm max. 8 mm max. using solid wire (2.5 mm 2 max.) using ferrule with insulative sleeve
h3dk-f 14 dimensions (unit: mm) timers track mounting products (sold separately) refer to page 28 for details. operating procedures basic operation timing charts note 1. the reset time is 0.1 s min. note 2. when power is supplied in flicker on start mode, the off indicator lights momentarily. this, however, has no effect on t he performance of the timer. 89.4 100 88.2 22.5 69.1 79 65.6 52 4 h3dk-f setting the time ranges use the on time range switch to set the on time range and the off time range switch to set the off time range. turn the switches with a flat-blade or phillips screwdriver. setting an on start or off start the on/off start switch can be used to switch between on-start and off-start operation. setting the times use the on time setting dial and the off time setting dial to set the on time and off time. setting the time ranges off time range switch on time range switch setting the on/off start switch on/off start switch setting the times on time setting dial off time setting dial flicker off start flicker on start t on t off t off t off t off t on t on : on set time t off : off set time on off on off on off on off power (a1 and a2) on indicator (15 and 18) off indicator (15 and 16) 0.1 s min. output (15 and 18) t off t off t on t on t on t on on off on off on off on off t on : on set time t off : off set time power (a1 and a2) on indicator (15 and 18) off indicator (15 and 16) 0.1 s min. output (15 and 18)
15 new product news  set two time ranges between 1 and 120 s with one timer.  models with 240 to 440-vac power supply added to series. lr ordering information list of models accessories (order separately) model structure *1. except for the h3dk-ge. specifications time ranges ratings operating modes supply voltage control output h3dk-g star-delta timer 24 to 240 vac/dc contact outputs delta circuit: spdt, star circuit: spdt model h3dk-g 12 vdc model h3dk-ga 240 to 440 vac model h3dk-ge item specification model mounting track 50 cm (l) x 7.3 mm (t) pfp-50n 1 m (l) x 7.3 mm (t) pfp-100n 1 m (l) x 16 mm (t) pfp-100n2 end plate --- pfp-m spacer --- pfp-s model terminal block operating/resetting method output type mounting method safety standards accessories h3dk-g 9 terminals time-limit operation/self- resetting time-limit (relay) star circuit: spdt delta circuit: spdt din track mounting curus *1 (ul 508 csa c22.2 no. 14) en 61812-1 iec 60664-1 4 kv/2 en 50274 user label time range setting t1x1 t1x10 star set time (t1) range 1 to 12 s 10 to 120 s star-delta transfer time (t2) select from 0.05, 0.1, 0.25, or 0.5 s. h3dk-g, -ga h3dk-ge power supply voltage *1  24 to 240 vac/dc, 50/60 hz *2  12 vdc *2  240 to 440 vac (50/60 hz) *6 allowable voltage fluctuation range  24 to 240 vac/dc: 85% to 110% of rated voltage  12 vdc: 90% to 110% of rated voltage 80 % to 110% of rated voltage power reset minimum power-off time: 0.5 s reset voltage 10% of rated voltage power consumption h3dk-g at 240 vac: 6.6 va max. *3 at 440 vac: 34 va max. h3dk-ga at 12 vdc: 0.9 w max. control output contact output (time-limit output: relay, star output: spdt, delta output: spdt): 5 a at 250 vac with resistive load (cos = 1) 5 a at 24 vdc with resistive load *3, *4 ith 2 a ac-15 120 vac: 1.5 a ac-15 240 vac: 1 a ac-15 440 vac: 0.3 a ambient operating temperature ? 20 to 55 c (with no icing) storage temperature ? 40 to 70 c (with no icing) ambient operating humidity 25% to 85% star-delta timer h3dk-g
h3dk-g 16 *1. when using a 24-vdc power supply voltage, there will be an inrush current of approximately 0.25 a. allow for this inrush cur rent when turning on and off the power supply to the timer with device with a solid-state output, such as a sensor. *2. dc ripple: 20% max. *3. refer to dc power consumptions (reference information) on page 27 for dc power consumptions. *4. the control output ratings are for one h3dk operating alone. if you operate two or more timers side by side, refer to installation pitch and output switching capacity (reference values) on the next page. *5. 125 vdc: 0.15 a max. with resistive load, 125 vdc: 0.1 a with l/r of 7 ms. minimum load: 10 ma at 5 vdc (p level, reference value) *6. for the h3dk-ge, approx. 6 a of inrush current will flow when the power supply is turned on . when selecting the device conne cted to the timer, allow leeway in the current ratings. characteristics installation pitch and output switching capacity (reference values) the relation between the installation pitch and the load current is shown in the fol- lowing graph. (except for the h3dk-ge) if timer is used under load conditions that exceed the specified values, the tempera- ture inside the timer will increase, reduc- ing the life expectancy of internal parts. 0 1 2 3 4 5 6 80 70 60 50 40 30 20 10 d = 5 mm d = 0 mm d = 10 mm d = 50 mm ambient temperature (c) maximum ambient operating temperature in specifications load current (a) din track timer installation pitch: d tested timer: h3dk-g applied voltage: 240 vac installation pitch: 0, 5, 10, and 50 mm test timer 1 test timer 2 test timer 3 te s t timer 4 te s t timer 5 testing method * except for the h3dk-ge h3dk-g, -ga h3dk-ge accuracy of operating time 1% of fs max. setting error 10% of fs 0.05 s max. transfer time total error (25% of transfer time + 5 ms) max. influence of voltage 0.5% of fs max. influence of tempera- ture 2% of fs max. insulation resistance 100 m ? min. at 500 vdc dielectric strength between current-carrying metal parts and exposed non-current-carrying metal parts: 2,000 vac 50/60 hz for 1 min. between control output terminals and operating circuit: 2,000 vac 50/60 hz for 1 min. between contacts not located next to each other: 1,000 vac 50/60 hz for 1min. between current-carrying metal parts and exposed non-current-carrying metal parts: 2,500 vac 50/60 hz for 1 min. between control output terminals and operating circuit: 2,500 vac 50/60 hz for 1 min. between contacts not located next to each other: 1,000 vac 50/60 hz for 1min. impulse withstand volt- age h3dk-g: 24 to 240 vac/vdc: 3 kv between power terminals, 4.5 kv between current-carrying metal parts and exposed non-current- carrying metal parts h3dk-ga: 12 vdc: 1 kv between power terminals, 1.5 kv between current-carrying metal parts and exposed non-current-carrying metal parts --- noise immunity square-wave noise generated by noise simulator (pulse width: 100 ns/1 s, 1-ns rise): 1.5 kv* static immunity malfunction: 4 kv, destruction: 8 kv vibration resistance destruction 0.75-mm single amplitude at 10 to 55 hz for 2 h each in 3 directions malfunction 0.5-mm single amplitude at 10 to 55 hz for 10 min each in 3 directions shock re- sistance destruction 1,000 m/s 2 3 times each in 6 directions malfunction 100 m/s 2 3 times each in 6 directions life ex- pectancy mechanical 10 million operations min. (under no load at 1,800 operations/h) 10 million operations min. (under no load at 1,800 operations/h) electrical 100,000 operations min. (5 a at 250 vac, resistive load at 360 operations/h) 100,000 operations min. (0.3 a at 440 vac, resistive load at 1,800 operations/h) degree of protection ip30 (terminal block: ip20) weight approx. 120 g
h3dk-g 17 applicable standards *1. this standard is not applicable to the h3dk-ge. *2. this standard is not applicable if the output is used with a rating that exceeds 250 vac. i/o connections safety standards curus: ul 508/csa c22.2 no. 14 *1 en 50274: finger protection, back-of-hand proof en 61812-1: pollution degree 2, overvoltage category iii *2 ccc: pollution degree 2, overvoltage category ii, section db14048.5-2008 part 5-1 lr: test specification no. 1-2002 category env 1.2 *1 emc (emi) en61812-1 radiated emissions: en 55011 class b emission ac mains: en 55011 class b harmonic current: en 61000-3-2 *1 voltage fluctuations and flicker: en61000-3-3 *1 (ems) en61812-1 esd immunity: en 61000-4-2: 6 kv contact discharge, 8 kv air discharge radiated radio-frequency electromagnetic field immunity (am radio waves): en 61000-4-3: 10 v/m (80 mhz to 1 ghz) burst immunity: en 61000-4-4: 2 kv power line, 1 kv i/o signal line surge immunity: en 61000-4-5: 2 kv common mode, 1 kv differential mode input none output control output the star output is turned off when the dial set value is reached and the delta output is turned on after the preset transfer time elapses. block diagrams h3dk-g indicator circuit ac (dc) input star output power supply circuit star time setting switch star-delta transfer time switch output circuit delta output star output on indicator delta output on indicator one-chip microcomputer ram rom clock terminal arrangement h3dk-g note: the power supply terminals do not have po- larity. a1 15 25 2628 a2 18 16 15 r1 1618 25 r2 2628 a2 a1 15 1816 25 2826 (din notation) star contacts delta contacts
h3dk-g 18 nomenclature terminal block (see notes 1 and 2.) main dial (sets the star time.) bottom view front view user label attachment location star operation indicator (green) star-delta transfer time switch delta operation indicator (orange) bottom view front view main dial (sets the star time.) user label attachment location star operation indicator (green) star-delta transfer time switch delta operation indicator (orange) terminal block (see notes 1 and 2.) front cover (see note 3.) h3dk- g note 1. use solid wire (2.5 mm 2 max.) or fer- rules with insulative sleeves to connect to the terminals. to maintain the withstand voltage after connecting the terminals, insert no more than 8 mm of exposed conductor into the terminal. recommended ferrules phoenix contact ai @@@ series  ai-twin @@@ series note 2. screw tightening torque recommended torque: 0.49 nm maximum torque: 0.98 nm note 3. always keep the front cover mounted when using the timer. 8 mm max. 8 mm max. using solid wire (2.5 mm 2 max.) using ferrule with insulative sleeve h3dk-ge
h3dk-g 19 dimensions (unit: mm) timers track mounting products (sold separately) refer to page 28 for details. 89.4 100 88.2 69.1 79 65.6 52 22.5 4 89.4 88.2 69.1 102 55 65.6 79 4 22.5 26 h3dk-g h3dk-ge
h3dk-g 20 operating procedures basic operation setting the delta time range and the star-delta transfer time (t2) star time (t1) range set the star-delta transfer time. for 1 (1 to 12 s), use side (a) (labeled ?t1 1?). for 10 (10 to 120 s), use side (b) (labeled ?t10 1?). (see following diagram.) setting the time the start time is set with the main dial. timing chart setting the time ranges t2 t2 0.5s 0.25s 0.1s 0.05s 0.5s 0.25s 0.1s 0.05s t1x10 t1x1 (a) (b) star-delta transfer time setting (t2) switches the start time (t1) range. setting the time main dial note: ?t1? is the start set time. ?t2? is the transfer time. on off on off on off on off on off t 1 t 2 t 1 : star time setting t 2 : transfer time power (a1 and a2) star contacts (15 and 18) delta contacts (25 and 26) 0.5 s min. star operation indicator delta operation indicator
21 new product news power off-delay timer h3dk-h  set two time ranges with each ti mer, from 0.1 to 12 seconds for the s series and from 1.0 to 120 seconds for the l series. ordering information list of models accessories (order separately) model structure specifications time ranges ratings operating modes supply voltage control output h3dk-h s series (time range: 0.1 to 12 s) l series (time range: 1.0 to 120 s) power off delay 100 to 120 vac contact output: spdt model h3dk-hcs h3dk-hcl 200 to 240 vac contact output: spdt model h3dk-hds h3dk-hdl 24 to 48 vac/dc contact output: spdt model h3dk-hbs h3dk-hbl item specification model mounting track 50 cm (l) x 7.3 mm (t) pfp-50n 1 m (l) x 7.3 mm (t) pfp-100n 1 m (l) x 16 mm (t) pfp-100n2 end plate --- pfp-m spacer --- pfp-s model terminal block operating/resetting method output type mounting method safety standards accessories h3dk-h 6 terminals instantaneous operation/ time-limit reset relay, spdt din track mounting curus (ul 508 csa c22.2 no. 14) en 61812-1 iec 60664-1 4 kv/2 en 50274 user label s series l series time range setting x0.1 x1 x1 x10 set time range 0.1 to 1.2 s 1 to 12 s 1 to 12 s 10 to 120 s power on time 0.1 s min. 0.3 s min. scale numbers 12 supply voltage  100 to 120 vac, 50/60 hz  200 to 240 vac, 50/60 hz  24 to 48 vac/dc, 50/60 hz *1 allowable voltage fluctuation range 85% to 110% of rated voltage power consumption h3dk-hcs/-hcl at 120 vac: 11.7 va max. h3dk-hds/-hdl at 240 vac: 29.5 va max. h3dk-hbs/-hbl at 48 vac: 1.2 va max. *2 control output contact output, 5 a at 250 vac with resistive load (cos = 1), 5 a at 30 vdc with resistive load *2 ambient operating temperature ? 20 to 55 c (with no icing) storage temperature ? 40 to 70 c (with no icing) ambient operating humidity 25% to 85%
h3dk-h 22 *1. dc ripple: 20% max. (a single-phase, full-wa ve rectifying power supply can be connected.) *2. refer to dc power consumptions (reference information) on page 27 for dc power consumptions. *3. the control output ratings are for one h3dk operating alone. if you operate two or more timers side by side, refer to installation pitch and output switching capacity (reference values) on the next page. characteristics applicable standards i/o accuracy of operating time 1% of fs max. ( 1% 10 ms max. at 1.2-s range) setting error 10% of fs 0.05 s max. influence of voltage 0.5% of fs max. ( 0.5% 10 ms max. at 1.2-s range) influence of tempera- ture 2% of fs max. ( 2% 10 ms max. at 1.2-s range) insulation resistance 100 m ? min. at 500 vdc dielectric strength between current-carrying metal parts and exposed non-current-carrying metal parts: 2,000 vac 50/60 hz for 1 min. between control output terminals and operating circuit: 2,000 vac 50/60 hz for 1 min. between contacts not located next to each other: 1,000 vac 50/60 hz for 1min. impulse withstand volt- age between power supply terminals: 1 kv for 24-vac/dc and 48-vac/dc models, 3 kv for all other models. between current-carrying metal parts and exposed non-current-carrying metal parts): 1.5 kv for 24-vac/dc and 48-vac/dc models, 4.5 kv for all other models. noise immunity square-wave noise generated by noise simulator (pulse width: 100 ns/1 s, 1-ns rise): 1.5 kv (between power supply terminals) static immunity malfunction: 4 kv, destruction: 8 kv vibration resistance destruction 0.75-mm single amplitude at 10 to 55 hz for 2 h each in 3 directions malfunction 0.5-mm single amplitude at 10 to 55 hz for 10 min each in 3 directions shock re- sistance destruction 1,000 m/s 2 3 times each in 6 directions malfunction 100 m/s 2 3 times each in 6 directions life ex- pectancy mechanical 10 million operations min. (under no load at 1,200 operations/h) electrical 100,000 operations min. (5 a at 250 vac, resistive load at 1,200 operations/h) degree of protection ip30 (terminal block: ip20) weight approx. 120 g safety standards curus: ul 508/csa c22.2 no. 14 en 50274: finger protection, back-of-hand proof en 61812-1: pollution degree 2, overvoltage category iii ccc: pollution degree 2, overvoltage category ii, section db14048.5-2008 part 5-1 lr: test specification no. 1-2002 category env 1.2 emc (emi)en61812-1 radiated emissions:en 55011 class b emission ac mains:en 55011 class b harmonic current:en 61000-3-2 voltage fluctuations and flicker:en61000-3-3 (ems)en61812-1 esd immunity:en 61000-4-2: 6 kv contact discharge, 8 kv air discharge radiated radio-frequency electromagnetic field immunity (am radio waves): en 61000-4-3: 10 v/m (80 mhz to 1 ghz) burst immunity:en 61000-4-4: 2 kv power line, 1 kv i/o signal line surge immunity:en 61000-4-5: 2 kv common mode, 1 kv differential mode input none output control output the timer operates as soon as the timer is turned on. the timer starts timing when the power is turned off and the output is turned off when the time set on the dial elapses. installation pitch and output switching capacity (reference values) the relation between the installation pitch and the load current is shown in the fol- lowing graph. (except for the h3dk-ge) if timer is used under load conditions that exceed the specified values, the tempera- ture inside the timer will increase, reduc- ing the life expectancy of internal parts. 0 1 2 3 4 5 6 80 70 60 50 40 30 20 10 d = 5 mm d = 0 mm d = 10 mm d = 50 mm ambient temperature (c) maximum ambient operating temperature in specifications load current (a) din track timer installation pitch: d tested timer: h3dk-h applied voltage: 240 vac installation pitch: 0, 5, 10, and 50 mm test timer 1 te s t timer 2 test timer 3 te s t timer 4 te s t timer 5 testing method
h3dk-h 23 connections nomenclature block diagrams h3dk-h output circuit counting circuit oscillation circuit indicator circuit ac (dc) input power supply circuit time specification switches power interruption detection circuit terminal arrangement h3dk-h note 1: the above figure shows the terminal ar- rangement for a 24 to 48-vac/dc model. models with 100 to 120-vac or 200 to 240-vac power input do not have a dc input. note 2: the power supply terminals do not have polarity. a1 15 a2 18 16 15 r1 1618 a2 a1 15 1816 (din notation) terminal block (see notes 1 and 2.) bottom view main dial (for setting the time) front view time range switch (s series: 0.1 or 1, l series: 1 or 10) power indicator (green) (lit while the power is on.) user label attachment location h3dk-h note 1. use solid wire (2.5 mm 2 max.) or fer- rules with insulative sleeves to connect to the terminals. to maintain the withstand voltage after connecting the terminals, insert no more than 8 mm of exposed conductor into the terminal. recommended ferrules phoenix contact ai @@@ series ai-twin @@@ series note 2. screw tightening torque recommended torque: 0.49 nm maximum torque: 0.98 nm 8 mm max. 8 mm max. using solid wire (2.5 mm 2 max.) using ferrule with insulative sleeve
h3dk-h 24 dimensions (unit: mm) timers track mounting products (sold separately) refer to page 28 for details. operating procedures basic operation setting the time ranges the scale multiplier can be changed with the timer range switch. it can be changed between 0.1 s and 1 s for an s-series timer and between 1 s and 10 s for an l-series timer. setting the time the operation time is set with the main dial. timing charts 89.4 100 88.2 22.5 69.1 79 65.6 52 4 h3dk-h setting the time ranges time range switch setting the time main dial t: set time rt: minimum power-on time (the output may never turn on if the power is not on for at least this time.) on off on off on off rt t t rt power (a1 and a2) output relay: no (15 and 18) indicator s series: 0.1 s min. l series: 0.3 s min.
h3dk 25 safety precautions refer to safety precau tions for all timers. note: the following is common for all h3dk models. switching arcs or relay heating may cause fire or explosion. do not use the timer in the presence of inflammable or explosive gases. the h3dk series uses a transformerless power supply system. an electrical shock may occur if an input terminal is touched while power is being supplied. the inrush current will depend on the type of load and may influence the contact switching fre- quency and number of operations. check both the rated current and the inrush current, and allow leeway in the circuit design. the life of the output relay largely depends on the switching current and other switch conditions. consider the actual application conditions and do not exceed the rated load or electrical life. if the output relay is used beyond its service life, the contacts may fuse or burning may occur. also, never exceed the rated load current. when using a heater, also place a ther- mal switch in the load circuit. do not remove the external case. minor electric shock, fire, or equipment failure may sometimes occur. do not disassemble, mod- ify, or repair the timer or touch any internal parts.  use ferrules to wire the h3dk. if stranded wires are used, wire scraps may enter the timer, possibly shorting the circuits.  rapid changes in temperature or high humidity may cause condensation in timer circuits, possibly resulting in malfunc- tion or damage to components. check the application environ- ment.  store the timer within the rated ranges given for the timer model you are using. if the timer is stored below ? 20 c, allow it to warm up for three hours at room temperature before turn- ing on the power supply.  use the timer within the ambient operating temperature and ambient operating humidity ranges given for the timer model you are using.  use the time within the characteristics for water and oil expo- sure given for the timer model you are using.  do not use the timer in locations subject to excessive dust, corrosive gas, or direct sunlight.  do not use the timer in locations subject to vibration and shock. long-term exposure may damage the timer due to stress.  separate the timer from any sources of excessive static elec- tricity, such as forming materials and pipes carrying power or liquid materials.  maintain the variations in the power supply voltage to within the specified allowable range.  if a voltage that exceeds the rating is applied, internal compo- nents may be destroyed.  wire all terminals correctly.  use only the specified wires for wiring. applicable wire gauge: awg18 to awg22  install and clearly label a switch or circuit breaker so that the operator can quickly turn off the power supply.  if the timer is left in the timed out condition for a long period of time at high temperatures, internal components (such as elec- trolytic capacitors) may deteriorate quickly.  the exterior of the timer may be damaged by organic solvents (such as thinners or benzene), strong alkali, or strong acids.  for timers with ac power input, use a commercial power sup- ply for the power supply voltage. although some inverters give 50/60 hz as the output frequency, do not use an inverter out- put as the power supply for a timer. doing so may result in smoking or burning due to inte rnal temperature increases in the timer.  use the same type of wiring for all timer wiring.  when disposing of the timer, observe all local ordinances as they apply.  the timer may not operate properly in locations that are sub- ject to sulfide gas, such as in sewers or incinerators. products that are suitable for operation in sulfide gas are not available for omron timers or general control devices. seal the timer to isolate it from sulfide gas. if the timer cannot be sealed, omron can make special products with resistance to sulfide gas for some timers. ask your omron representative for details.  confirm that the power and output indicators are operating normally. depending on the operating environment, the indica- tors and plastic parts may deteriorate faster than expected, causing the indicators to fail. periodically perform inspections and replacements. caution precautions for safe use
h3dk 26 changing switch settings do not change the time unit, time scale, operating mode, or init/ time switch while the timer is in operation. doing so may result in malfunction. turn off the power supply before changing the setting of any switch. mounting and dismounting  although there are no particular mounting restrictions, the timer should be mounted as horizontally as possible.  when mounting the timer on a mounting track, loosen the two hooks, press the timer onto the track, and then insert the hooks.  when removing the timer, pull out the two hooks, and then remove the timer from the track  it will be easier to mount and dismount the timer if a distance of 30 mm or more is provided between the bottom of the timer and other equipment. power supply  the power supply can be connected to the power input termi- nals without considering polarity.  a dc power supply can be connected if its ripple factor is 20% or less and the average voltage is within the allowable voltage fluctuation range of the timer.  for the power supply of the input device, use an isolating transformer in which the primary and secondary windings are mutually isolated and the secondary winding is not grounded. (h3dk-m1 and h3dk-m2 only)  the h3dk-h has a large inrush current. provide sufficient power supply capacity. if the power supply capacity is too small, there may be delays in turning on the output. relationship between input and power supply cir- cuits (h3dk-m1/-m2)  the input circuit and the power supply circuit are configured independently. the input circuit can be turned on and off without considering the on/off state of the power supply. a voltage equivalent to the power supply voltage is also applied to the input circuit.  if a relay or transistor is connected to two or more timers, the input terminals of those timers must be wired properly so that they will not be different in phase or the terminals will be short- circuited to one another. always use the same power supply phases. environment  when using the timer in an area with excessive electronic noise, separate the timer and input device as far as possible from the noise sources. it is also recommended to shield the input signal wiring to prevent electronic interference.  the external impulse voltage entering across the power supply terminals has been checked against a 1.2 50 s standard waveform according to jec-210, impulse voltage/current test, of the institute of electrical engineers of japan. surge or noise superimposed on the power supply may damage internal components or cause them to malfunction. we recom- mend that you check the circuit waveform and use surge absorbers. the effects on components depend on the type of surge and noise that are generated. always perform testing with the actual equipment. precautions for correct use hook hook 30 mm min. hook hook a1 b1 a2 circuit power h3dk isolation transformer is required. rectifier circuit start input input circuit power supply circuit b1 a1 a2 ac/dc power supply h3dk h3dk power b1 a1 a2 a1 a2 b1 h3dk h3dk power b1 a1 a2 a1 a2 b1 contact or transistor for external input signal contact or transistor for external input signal
h3dk 27 wiring the h3dk-h acts like a high-impedance circuit. therefore, the timer may not reset if it is influenced by inductive voltage. to eliminate inductive voltage, the wires connected to the timer must be as short as possible and should not be installed parallel to power lines. if the timer is influenced by inductive voltage that is 30% or more of the rated voltage, connect a cr filter with a capacitance of approximately 0.1 f and a resistance of approx- imately 120 ? or a bleeder resistor between the power supply terminals. if there is any residual voltage due to current leakage, connect a bleeder resistor between the power supply terminals. operating frequency  the h3dk-h may malfunction if it is used as shown below. do not use the h3dk-h in these ways. timer repeatedly times out in cycles of 3 s or less in the above case, use the h3dk-m2/-m1 in d mode (signal off delay). dc power consumptions (reference information) other precautions  if the timer is mounted on a control panel, dismount the timer from the control panel before carrying out a voltage withstand test between the electric circuits and non-current-carrying metal parts of the timer. (otherwise, the internal circuits of the timer may be damaged.)  the h3dk-h uses a latching relay for the output. shock, such as dropping the h3dk-h during shipment or handling, can cause the output contacts to reverse to the neutral position. check the output status with a tester before using the h3dk- h.  the life expectancy of the control output contacts is greatly affected by switching conditions. always confirm operation using the actual conditions and equipment before using the timer and make sure that the number of switching operations presents no problems in performance. if timer application is continued after performance has deteriorated, insulation fail- ure between circuits, burning of the control output relay, or other problem will eventually occur.  if the power supply voltage is gradually increased, a power reset may occur or the timer may time out. use a switch, relay, or other device with contacts to apply the power supply voltage all at once.  make sure that residual voltage or inductive voltage is not applied after the power turns off.  error in the operation time of the timer is given as a percent- age of the full-scale time. the absolute value of the error will not change even if the set time is changed. therefore, always use the timer with the set time set as close as possible to the full-scale value of the set time range.  when switching a microload, check the specified minimum load given for the timer model you are using.  when setting the operating time, do not turn the dial beyond the scale range.  if better accuracy is required in the set time, adjust the dial while measuring the operation time.  if the timer is reset immediately after timing out, make sure that the circuit configuration allows sufficient resetting time. errors will occur in the sequence if there is not sufficient reset- ting time.  when directly switching a dc load, the switching capacity will be lower than when switching an ac load.  refer to the datasheet for the h3dk for cable selection and other conditions for compliance with emc standards.  the power supply terminals and input terminals are not iso- lated. there is basic insulation between the power supply ter- minals and output terminals.  if double or reinforced insulation is required, use the double or reinforced insulation defined in iec 60664 that is suitable for the maximum applied voltage for the clearance, solid insula- tion, and other factors. notice to users of the h3dk in the usa and canada please use the following installation information instead of the general information in this document in order to use the product under certified conditions of ul and csa when the product is installed in the usa or canada. these conditions are required by nfpa 70, national electrical code in the usa and the canadian electrical code, part i in canada and may vary from information given in this document.  use an isolated source for power input for the h3dk- @ a. use an isolated source with external overcurrent protection of 16 a maximum for the source and input. (the input is applica- ble to the h3dk-m only.)  environment surrounding air temperature: 55 c  power supply: the inputs are non-isolated (applicable to h3dk-m only). the same power supply as the main power source must be used for that for input.  pollution degree pollution degree ii h3dk-m2/-s2 at 24 vdc: 1.2 w max. h3dk-m1/-s1 at 24 vdc: 1.1 w max. h3dk-f at 24 vdc: 1.1 w max. h3dk-g at 24 vdc: 1.2 w max. h3dk-hbs/-hbl at 24 vdc: 1.2 w max. power output 3 s or less 3 s or less en/iec standard compliance precautions for compliance with ul standards and csa standards
h3dk 28 track mounting products (sold separately) (unit: mm) note 1: order the above products in multiples of 10. note 2: the tracks conform to din standards. 1 35 0.3 7.3 0.15 27 0.15 4.5 15 25 25 10 15 (5)* 10 25 25 *dimensions in parentheses are for the pfp-50n. 1,000 (500)* din track pfp-100n pfp-50n 15 25 25 1,000 4.5 25 25 15 10 1 242735 0.3 16 1.5 29.2 10 din track pfp-100n2 4.8 1.3 35.5 35.3 1.8 1 1.8 10 6.2 m4 screw and washer 50 11.5 10 m4x8 panhead screw end plate pfp-m 5 16 12 44.3 34.8 16.5 spacer pfp-s



warranty and application considerations read and understand this catalog please read and understand this catalog before purchasing the products. please consult your omron representative if you have any questions or comments. warranty and limitations of liability warranty omron's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by omron. omron makes no warranty or representation, express or implied, regarding non-infringement, merchantability, or fitness for particular purpose of the products. any buyer or user acknowledges that the buyer or user alone has determined that the products will suitably meet the requirements of their intended use. omron disclaims all other warranties, express or implied. limitations of liability omron shall not be responsible for special, indirect , or consequential damages, loss of profits, or commercial loss in any way connected with the products, whether such claim is based on contract, warranty, neglige nce, or strict liability. in no event shall the resp onsibility of omron for any act exceed the individual price of the product on which liability is asse rted. in no event shall omron be responsible for warranty, repair, or other claims regarding the products unless omron's analysis confirms that the products were properly handled, stored, installed, and maintained and not subject to contamination, abuse, misuse, or inappropriate modification or repair. application considerations suitability for use omron shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's application or use of the products. take all necessary steps to determine th e suitability of the product for the systems, machines, and equipment with which it wil l be used. know and observe all prohibitions of use applicable to this product. never use the products for an application involv ing serious risk to life or property without ensuring that the system as a whole has been designed to address the risks, and that the omron products are properly rated and installed for the intended use within the overall equipment or system. disclaimers performance data performance data given in this catalog is provided as a guide fo r the user in determining suitability and does not constitute a warranty. it may represent the result of omron's test conditions, and the users mu st correlate it to actual application requirements. actual performance is subject to the omron warranty and limitations of liability . change in specifications product specifications and accessories may be changed at any time based on improvements and other reasons. consult with your omron representative at any time to conf irm actual specifications of purchased product. dimensions and weights dimensions and weights are nominal and are not to be used fo r manufacturing purposes, even when tolerances are shown. all dimensions shown are in millimeters. to convert millimeters into inches , multiply by 0.03937. to convert gr ams into ounces, multiply by 0.03527. authorized distributor: in the interest of product improvement, specifications are subject to change without notice. cat. no. l118-e1-02 printed in japan 0910 ? omron corporation 2010 all rights reserved. omron corporation industrial automation company omron electronics llc one commerce drive schaumburg, il 60173-5302 u.s.a. tel: (1) 847-843-7900/fax: (1) 847-843-7787 regional headquarters omron europe b.v. wegalaan 67-69-2132 jd hoofddorp the netherlands tel: (31)2356-81-300/fax: (31)2356-81-388 contact: www.ia.omron.com tokyo, japan omron asia pacific pte. ltd. no. 438a alexandra road # 05-05/08 (lobby 2), alexandra technopark, singapore 119967 tel: (65) 6835-3011/fax: (65) 6835-2711 omron (china) co., ltd. room 2211, bank of china tower, 200 yin cheng zhong road, pudong new area, shanghai, 200120, china csm_3_1_ 0212 t el: (86) 21-5037-2222/fax: (86) 21-5037-2200


▲Up To Search▲   

 
Price & Availability of H3DKFACDC24240

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X